DocumentCode :
2388845
Title :
Straight through cold-applied shrinkable EPDM cable joints designed for high stress medium voltage EPR cables
Author :
Wen, Y. ; Shocket, A. ; Cinquemani, P.L. ; Vallauri, U. ; Lencot, G.
Author_Institution :
Pirelli Cables & Syst. North America, Lexington, SC, USA
fYear :
1998
fDate :
25-28 Oct 1998
Firstpage :
516
Abstract :
The introduction of high electrical stress EPR insulated medium voltage cables leads to the development of new cable joints suitable for installation. This paper presents the joint design considerations and test data. The test program is based on IEEE Standard 404-1993. Test samples include joints for high stress EPR cables and transition joints from high stress EPR cables to PILC cables. All test results have shown that both joint designs comply with the IEEE standard and suitable for operation in cable network systems
Keywords :
cable jointing; ethylene-propylene rubber; power cable insulation; EPDM cable joint; EPR cable; IEEE Standard 404-1993; PILC cable; electrical stress; insulation; Cable insulation; Cable shielding; Conductors; Dielectrics and electrical insulation; Medium voltage; Paramagnetic resonance; Rubber; Statistics; Stress; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on
Conference_Location :
Atlanta, GA
Print_ISBN :
0-7803-5035-9
Type :
conf
DOI :
10.1109/CEIDP.1998.732949
Filename :
732949
Link To Document :
بازگشت