    Testing continuity of grounding grid using the AC current injection method

  • Author

    Ma, Yan ; Karady, George G. ; Kucuksari, Sadik

  • Author_Institution
    Sch. of Electr., Comput., & Energy Eng., Arizona State Univ., Tempe, AZ, USA
  • fYear
    2010
  • fDate
    25-29 July 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    We propose here a cost-effective, realistic method for testing the continuity of the grounding grid and for identifying its weak points or discontinuities. The proposed method involves injecting an ac current of ~200 A frequency not 60 Hz or 60 Hz harmonic into a grounding grid. The purpose of the frequency setting is to be able to distinguish the magnetic field produced by the injected current when the substation is energized. The magnetic field generated by the current flowing in the buried grid conductors is then measured above the ground. A strong magnetic field indicates that the grounding grid is in good condition; a weak magnetic field indicates that some damage may exist. Two field tests were conducted to demonstrate that the proposed method works effectively in determining the continuity of the grounding grid.
  • Keywords
    earthing; magnetic fields; power grids; substations; AC current injection method; buried grid conductors; frequency setting; grounding grid; strong magnetic field; substation; weak discontinuities; weak points; Continuity; grounding; grounding grids; substation grounding;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting, 2010 IEEE
  • Conference_Location
    Minneapolis, MN
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-6549-1
  • Electronic_ISBN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PES.2010.5590219
  • Filename
    5590219