Title
Testing continuity of grounding grid using the AC current injection method
Author
Ma, Yan ; Karady, George G. ; Kucuksari, Sadik
Author_Institution
Sch. of Electr., Comput., & Energy Eng., Arizona State Univ., Tempe, AZ, USA
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
6
Abstract
We propose here a cost-effective, realistic method for testing the continuity of the grounding grid and for identifying its weak points or discontinuities. The proposed method involves injecting an ac current of ~200 A frequency not 60 Hz or 60 Hz harmonic into a grounding grid. The purpose of the frequency setting is to be able to distinguish the magnetic field produced by the injected current when the substation is energized. The magnetic field generated by the current flowing in the buried grid conductors is then measured above the ground. A strong magnetic field indicates that the grounding grid is in good condition; a weak magnetic field indicates that some damage may exist. Two field tests were conducted to demonstrate that the proposed method works effectively in determining the continuity of the grounding grid.
Keywords
earthing; magnetic fields; power grids; substations; AC current injection method; buried grid conductors; frequency setting; grounding grid; strong magnetic field; substation; weak discontinuities; weak points; Continuity; grounding; grounding grids; substation grounding;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5590219
Filename
5590219
Link To Document