Abstract
This paper presents the measured impedance at the relaying point in the presence of one of the series connected flexible alternating current transmission system (FACTS) devices, i.e. static synchronous series compensator (SSSC). The presence of SSSC on a transmission line greatly influences the tripping characteristic of distance relays. Distance relay tripping characteristic itself depends on the power system structural conditions (short circuit levels at the line ends), pre-fault loading (load angle and voltage magnitude ratio of the line ends), and especially the ground fault resistance. In the presence of SSSC, its controlling parameters as well as its connection point also affect the tripping characteristic. Here, the measured impedance at the relaying point is calculated due to the mentioned affecting parameters.
Keywords
flexible AC transmission systems; power transmission protection; relay protection; static VAr compensators; FACTS devices; SSSC; distance relay tripping characteristic; flexible alternating current transmission system; ground fault resistance; static synchronous series compensator; Current measurement; Distributed parameter circuits; Flexible AC transmission systems; Impedance measurement; Power system faults; Power system measurements; Power system relaying; Power transmission lines; Protective relaying; Transmission line measurements; Distance protection; FACTS devices; Fault resistance; SSSC; Tripping characteristic;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Conference, 2006. PECon '06. IEEE International
Conference_Location
Putra Jaya
Print_ISBN
1-4244-0273-5
Electronic_ISBN
1-4244-0274-3
Type
conf
DOI
10.1109/PECON.2006.346726
Filename
4154570
Link To Document