Addressing nuisance tripping of instantaneous trip breakers in high efficiency motor applications
Author :
Heberlein, G. Erich, Jr.
Author_Institution :
Allen-Bradley Co., Milwaukee, WI, USA
fYear :
1989
fDate :
19-23 June 1989
Firstpage :
53
Lastpage :
61
Abstract :
Reviewing the motor starting current phenomena from high-efficiency motors and the National Electric Code requirements for instantaneous circuit breakers, the author has determined that there are conflicts. To address this situation, the author is proposing changes to the National Electric Code and the addition of new test requirements for the qualification or listing of the coordinated protective combination starters. With this in place, new guidelines for settling the adjustment of instantaneous circuit breakers in high-efficiency motor applications are established. It is noted that this new method is easier for the user to apply, permits higher trip settings to address nuisance tripping on high-efficiency motor applications, and provides improved coordination protection.<>
Keywords :
circuit breakers; electric motors; National Electric Code; coordinated protective combination starters; coordination protection; high efficiency motor; instantaneous trip circuit breakers; nuisance tripping; Circuit breakers; Circuit faults; Guidelines; Manufacturing; National electric code; Proposals; Protection; Protective relaying; Rotors; Steady-state;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 1989., Conference Record of 1989 Annual
Conference_Location :
Atlanta, GA, USA
Type :
conf
DOI :
10.1109/PAPCON.1989.36935
Filename :
36935
Link To Document :
بازگشت