DocumentCode :
2397828
Title :
Ground Fault Location in Low-Voltage High-Resistance Grounded Systems via the Single-Processor Concept for Circuit Protection
Author :
Valdes, Marcelo ; Papallo, Tom ; Premerlani, Bill
Author_Institution :
GE, Plainville, CT
fYear :
2006
fDate :
18-23 June 2006
Firstpage :
1
Lastpage :
8
Abstract :
Low-voltage resistance-grounded systems may provide significant advantages to the facility in terms of system reliability and safety. However, maintenance of these systems is more complex than for solidly grounded wye systems and improper first-fault isolation and lack of timely repair may present a risk to the facility. Identifying the location of ground faults within the distribution system is the main problem. We describe a new way to detect which feeder has been faulted in a lineup of low-voltage switchgear protected via the "single-processor concept for protection and control of circuit breakers in low-voltage switchgear", M.E. Valdes (2004). We describe the detection methodology and how the potential sources of error are addressed
Keywords :
circuit breakers; earthing; fault location; paper industry; paper mills; power distribution faults; power distribution protection; circuit breakers; circuit protection; distribution system; first-fault isolation; ground faults location; low-voltage high-resistance grounded systems; low-voltage switchgear; single-processor concept; solidly grounded wye systems; Circuit faults; Electrical fault detection; Fault detection; Fault diagnosis; Fault location; Maintenance; Protection; Reliability; Safety; Switchgear; fault detection; low-voltage high-resistance grounding; single-processor concept;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 2006. Conference Record of Annual
Conference_Location :
Appleton, WI
Print_ISBN :
1-4244-0281-6
Type :
conf
DOI :
10.1109/PAPCON.2006.1673771
Filename :
1673771
Link To Document :
بازگشت