• DocumentCode
    2398070
  • Title

    Use of Instantaneous Trip Functions and Current Limiting Fuses to Reduce Arc Flash Energy

  • Author

    Nepveux, Felix

  • Author_Institution
    Jacobs Eng., Greenville, SC
  • fYear
    2006
  • fDate
    18-23 June 2006
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    The instantaneous trip can be used to reduce arc flash energy levels at 600 volt and 5 kV MCCs by minimizing the time to clear faults. The instantaneous is often not used since coordination with large motor starters can be lost. Which is more important? A digital multifunction relay may be able to use the Fourier transform algorithms for the instantaneous trip function to improve coordination with current limiting fuses in starters
  • Keywords
    Fourier transforms; arcs (electric); current limiters; electric fuses; electrical accidents; electrical safety; fault currents; paper industry; relays; starting; Fourier transform algorithms; arc flash energy reduction; current limiting fuses; digital multifunction relay; instantaneous trip functions; motor starters; Current limiters; Digital relays; Energy states; Fourier transforms; Fuses;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Pulp and Paper Industry Technical Conference, 2006. Conference Record of Annual
  • Conference_Location
    Appleton, WI
  • Print_ISBN
    1-4244-0281-6
  • Type

    conf

  • DOI
    10.1109/PAPCON.2006.1673786
  • Filename
    1673786