Mitigation method of 3rd-harmonic voltage for a three-phase four-wire distribution system based on a series active filter for the neutral conductor
Author :
Wada, Keiji ; Shimizu, Toshihisa
Author_Institution :
Dept. of Electr. Eng., Tokyo Metropolitan Univ., Japan
Volume :
1
fYear :
2002
fDate :
13-18 Oct. 2002
Firstpage :
64
Abstract :
This paper proposes a series active filter for mitigation of the 3rd-harmonic voltage in a three-phase four-wire power distribution system in a building. The active filter which consists of a single-phase inverter can suppress the harmonic voltage of the system. The active filter is characterized by acting not only as a capacitor but also as a resistor for the 3rd-harmonic components. A Hilbert transformer is applied to the controller of the active filter in order to realize the accurate 3rd-harmonic detection on a single-phase active filter. Measurement results of harmonic distortion of source voltage in a building are also shown in this paper. It is clarified in a simulation and experiment that the active filter can suppress the 3rd-harmonic voltage without increasing neutral conductor current.
Keywords :
Hilbert transforms; active filters; building wiring; distribution networks; harmonic distortion; power harmonic filters; power system harmonics; Hilbert transformer; neutral conductor series active filter; source voltage harmonic distortion measurement; third-harmonic voltage mitigation method; three-phase four-wire building distribution system; total harmonic distortion; Active filters; Capacitors; Conductors; Distortion measurement; Harmonic distortion; Inverters; Power distribution; Power harmonic filters; Resistors; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Conference, 2002. 37th IAS Annual Meeting. Conference Record of the
Conference_Location :
Pittsburgh, PA, USA
ISSN :
0197-2618
Print_ISBN :
0-7803-7420-7
Type :
conf
DOI :
10.1109/IAS.2002.1044068
Filename :
1044068
Link To Document :
بازگشت