DocumentCode :
2404681
Title :
An analysis of the National Electrical Code® requirements for Critical Operations Power Systems (COPS) and the effect on refineries and petrochemical facilities
Author :
Guidry, Paul E. ; Mehmood, Wahab
Author_Institution :
Fluor Enterprises, Inc., Sugar Land, TX, USA
fYear :
2011
fDate :
19-21 Sept. 2011
Firstpage :
1
Lastpage :
9
Abstract :
During the 2008 National Electrical Code (NEC) [1] cycle, Article 708, Critical Operations Power Systems (COPS), was introduced. As stated in Article 708, Scope, “the provisions of this article apply to the installation, operation, monitoring, control and maintenance of the portions of the premises wiring system intended to supply, distribute, and control electricity to designated critical operations areas (DCOA) in the event of disruption to elements of the normal system.” Refineries and some petrochemical facilities may be included in this scope due to the criticality of their continuous operation. The purpose of this paper is to analyze the effect the new requirements that a hardened electrical system will have upon design and engineering for these facilities. Key points are 1) risk assessment of the system, 2) power distribution requirements, 3) power sources and, 4) documentation of the emergency operations plan, all based on NEC [2] requirements and NFPA 1600-2010 [4], Standard on Disaster/Emergency Management and Business Continuity Programs. The term “hardened” in this paper is used to describe an installation that is highly resistant to damage or disruption and having a high degree of resiliency and dependability.
Keywords :
electrical installation; electrical safety; petrochemicals; risk management; wiring; COPS; NFPA 1600-2010; National Electrical Code; business continuity programs; critical operations power systems; designated critical operations areas; emergency operations plan; petrochemical facilities; power distribution requirements; power sources; premises wiring system; refineries; risk assessment; standard on disaster-emergency management; Hazards; National Electrical Code; Power distribution planning; Power system reliability; Reliability engineering; Risk management; COPS; Critical Operations Power Systems; DCOA; Designated Critical Operations Areas; National Electrical Code; National Fire Protection Association; Risk Assessment;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Petroleum and Chemical Industry Conference (PCIC), 2011 Record of Conference Papers Industry Applications Society 58th Annual IEEE
Conference_Location :
Toronto, ON
ISSN :
0090-3507
Print_ISBN :
978-1-61284-299-8
Type :
conf
DOI :
10.1109/PCICon.2011.6085865
Filename :
6085865
Link To Document :
بازگشت