DocumentCode
2409041
Title
Measurement of moisture spatial profiles in transformer pressboard
Author
Mamishev, A.V. ; Du, Y. ; Lesieutre, B.C. ; Zaha, M.
Author_Institution
Dept. of Electr. Eng. & Comput. Sci., MIT, Cambridge, MA, USA
Volume
1
fYear
1998
fDate
25-28 Oct 1998
Firstpage
323
Abstract
Moisture concentration was measured in a 1.5 mm thick transformer pressboard as a function of time and position during moisture diffusion process. A flexible interdigital three-wavelength sensor was used to provide the necessary information regarding pressboard dielectric properties at different depths from the sensor-pressboard interface. Results were obtained by processing the signals from the three-wavelength sensor, air humidity sensor, and thermocouple installed in the experimental chamber. Air-pressboard equilibrium curves were used to provide boundary conditions and the relative moisture level magnitude. The proposed technology has significant potential for measurement of diffusion processes in various dielectrics
Keywords
humidity sensors; insulation testing; moisture measurement; power transformer insulation; thermocouples; 1.5 mm; air humidity sensor; air-pressboard equilibrium curves; boundary conditions; flexible interdigital three-wavelength sensor; moisture concentration; moisture diffusion process; moisture spatial profiles; relative moisture level magnitude; sensor-pressboard interface; thermocouple; three-wavelength sensor; transformer pressboard; Boundary conditions; Dielectric measurements; Diffusion processes; Humidity; Moisture measurement; Position measurement; Signal processing; Thermal sensors; Thickness measurement; Time measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on
Conference_Location
Atlanta, GA
Print_ISBN
0-7803-5035-9
Type
conf
DOI
10.1109/CEIDP.1998.733995
Filename
733995
Link To Document