DocumentCode :
2415227
Title :
Nonlinear fuzzy model for operating condition evaluation of power cables in tunnels
Author :
Sui, Hui-bin ; Li, Ke-jun ; Sun, Ying ; Liu, Meng
Author_Institution :
Sch. of Electr. Eng., Shandong Univ., Jinan, China
fYear :
2012
fDate :
7-11 Oct. 2012
Firstpage :
1
Lastpage :
6
Abstract :
To assure the construction and operation security of the smart grid, it is necessary to assess the real-time operation reliability of the power cables which work in power tunnels by using on-line monitoring data. An online assessment system, which presents the important operating characteristics of the power cables, has been built up based on the following data: some preventive experiments results data, working environment, operation records, maintenance records, etc. With analytic hierarchy process method, an improved fuzzy integrated evaluation assessment model for cable assessment is proposed, the relative interiority indicator is adopted, and different methods are used to determine the membership functions for the qualitative indices and the quantitative indices. Through assessing the layer and sub-layer factors, the comprehensive operating conditions of the cables can be estimated. Based on the actual monitor data for a 220kV cable in power tunnel, the analysis result shows the proposed assessment model is correct and effective.
Keywords :
fuzzy set theory; maintenance engineering; power cables; power system security; smart power grids; tunnels; analytic hierarchy process method; fuzzy integrated evaluation assessment model; maintenance records; nonlinear fuzzy model; online assessment system; online monitoring data; operation records; power cables; power tunnels; qualitative indices; quantitative indices; real-time operation reliability; relative interiority indicator; smart grid construction; smart grid operation security; sublayer factors; voltage 220 kV; Communication cables; Monitoring; Power cables; Security; Smart grids; Temperature measurement; Analytic hierarchy process; fuzzy integrated evaluation; on-line operating condition assessment; power cable; power tunnels;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industry Applications Society Annual Meeting (IAS), 2012 IEEE
Conference_Location :
Las Vegas, NV
ISSN :
0197-2618
Print_ISBN :
978-1-4673-0330-9
Electronic_ISBN :
0197-2618
Type :
conf
DOI :
10.1109/IAS.2012.6374112
Filename :
6374112