Title :
The improvement in the reliability problem for air current breaker´s over current protect function
Author :
Cheng-Chung Chien ; Chang, C.N. ; Yung-Tang Wu ; Tseng, C.C. ; Chiu, D.H. ; Wan, J.K. ; Wu, C.S. ; Hsu, C.T. ; Chen, E.D. ; Li, F.H. ; Shao, T.H.
Author_Institution :
Tainwan Semicond. Manuf. Co. Ltd., Hsinchu, Taiwan
Abstract :
Almost all plants have the experience of ACB´s overcurrent relay (OCR) unexpectedly trip event. Each accident will cause a huge production loss. But manufacturers of OCR can´t afford the cost-effective solution of problem. The most used solution is to install an additional relay (ex. ABB Relay B) to replace the function of the ACB´s OCR or to adopt a new ACB to replace the old one. These two uneconomical solutions are not only high cost but also time consumption on annual PM. Thus, authors proposed a novel solution by interlocking the main ACB´s relay and the feeder ACB´s OCR function to prevent the ACB tripped by OCR false tripping signal. This method does not require additional relay and current transformer. Therefore, it is a cost-effective and time saving solution.
Keywords :
circuit breakers; overcurrent protection; power system reliability; ACB overcurrent relay; OCR function; air current breaker overcurrent protect function; false tripping signal; reliability problem improvement; Circuit faults; Coils; Companies; Fault currents; Monitoring; Optical character recognition software; Relays; Abnormal trip; Air Circuit Breaker (ACB); Overcurrent relay (OCR);
Conference_Titel :
Industrial Engineering and Engineering Management (IEEM), 2012 IEEE International Conference on
Conference_Location :
Hong Kong
DOI :
10.1109/IEEM.2012.6837893