Evaluation of gas insulated substations and circuit breakers using partial discharge - IMS
Author :
Pilzecker, P. ; Baumbach, J.I.
Author_Institution :
G.A.S. Gesellschaft fur Anal. Sensorsyst. mbH, Technologie Zentrum Dortmund, Germany
fYear :
2002
fDate :
7-10 Apr 2002
Firstpage :
399
Lastpage :
402
Abstract :
Despite the high reliability of modern gas insulated switch gear and substations (GIS), failures still occur in their long term operation. Some of these failures are preceded to small variations of gas compositions within the shielded compartments of a GIS. Thus the prediction of the gas quality within the compartment should be attainable on the basis of a sensitive analytical monitoring system, by sensing the insulating gas continuously. Such a monitoring system for GIS and SF6-filled circuit breakers was realised on the basis of ion mobility spectrometers (IMS). Especially, partial discharge IMS provides power utilities a diagnostic tool able to perform on-site monitoring and event controlled inspections of the SF6 gas. The results of on-site monitoring as well as on-line analysis of SF6 contained in a circuit breaker of a GIS in Germany, before and after operation are described and the relation between switching and the remaining number of decomposition products in SF6 is shown and discussed on the basis of the signal delivered by the PD-IMS used. Conclusions arising from investigations on different circuit breakers in different substations in Germany are presented. The details of some case studies are considered, indicating that a full recombination of decomposition products was not achieved in all cases. Results of investigations of different disconnecting switches in a substation in Germany are presented also. In a special case at one switch the prevention of a failure is presented. Finally, the structure of an automatic system for continuous on site sensing of SF6-decomposition in a hydroelectric power plant in Brasil is discussed.
Keywords :
computerised monitoring; gas insulated substations; gas insulated switchgear; ion mobility; partial discharge measurement; Brazil; Germany; SF6; circuit breakers; decomposition products; disconnecting switches; event controlled inspections; failure prevention; gas insulated circuit breakers; gas insulated substations; gas insulated switch gear; gas quality prediction; hydroelectric power plant; insulating gas sensing; ion mobility spectrometers; monitoring system; on-site monitoring; partial discharge; shielded compartments; Circuit breakers; Condition monitoring; Gas insulation; Gears; Geographic Information Systems; Partial discharges; Spectroscopy; Substations; Switches; Switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 2002. Conference Record of the 2002 IEEE International Symposium on
Print_ISBN :
0-7803-7337-5
Type :
conf
DOI :
10.1109/ELINSL.2002.995960
Filename :
995960
Link To Document :
بازگشت