    Verification of the operation reliability by suitable test procedures for GIL

  • Author

    Finkel, M. ; Boeck, W. ; Kynast, E.

  • Author_Institution
    Inst. for High Voltage Eng. & Electr. Power Transmission, Tech. Univ. Munich, Germany
  • fYear
    2002
  • fDate
    7-10 Apr 2002
  • Firstpage
    430
  • Lastpage
    434
  • Abstract
    The breakdown distribution functions are presented for arrangements with quasi-homogeneous field distribution and the maximum reduction of the electrical strength due to the area effect is determined. Furthermore, the influence of critical defects is discussed with respect to the on-site tests and the operation reliability. It is shown that the operation reliability of GIL can be verified with the test procedures approved for GIS.
  • Keywords
    SF6 insulation; electric breakdown; electric strength; impulse testing; insulation testing; power transmission lines; reliability; GIS; SF6; area effect; breakdown distribution; breakdown distribution functions; critical defects; electrical strength reduction; gas insulated substations; impulse testing; on-site tests; operation reliability; quasi-homogeneous field distribution; test procedures; Breakdown voltage; Dielectrics and electrical insulation; Distribution functions; Electric breakdown; Gas insulated transmission lines; Gas insulation; Impulse testing; Insulation testing; Sulfur hexafluoride; System testing;