Abstract :
In a coaxial test apparatus enabling the measurement of voltage and current at the test gap, dc conduction and breakdown in transformer oil caused by the application of dc voltages are investigated. Current measurements cover the range from 10-1 A to 1 kA, with temporal resolutions of milliseconds at the lowest current amplitudes to sub-nanoseconds for currents larger than 10-4 A. The dc current/voltage characteristic for sub-breakdown voltage amplitudes point to the injection of charge carriers, allow us to characterize the transport mechanisms, and the influence of space charges. For voltages approaching breakdown thresholds, quasi dc-currents rising from nanoamperes to microamperes are superimposed by current pulses with amplitudes of milliamperes and above, and durations of nanoseconds. The onset of these current pulses occurs up to 10 μs before breakdown. One of these current pulses reaches a critical amplitude causing voltage breakdown and current rise to the impedance-limited value within 2 ns. Additional optical diagnostics using photomultipliers and high-speed photography with gated microchannel plates yield information on hydrodynamic processes and charge carrier amplification mechanisms associated with the current pulses and final breakdown, such as bubble formation, as well as on the development of the spark plasma finally bridging the gap.
Keywords :
electric breakdown; electrical conductivity; transformer oil; 10 mus; 10-1 A to 1 kA; 10-4 A; breakdown; charge carrier amplification mechanisms; charge carriers injection; coaxial test apparatus; conduction; current; dc conduction; hydrodynamic processes; quasi dc-currents; sub-breakdown voltage amplitudes; temporal resolutions; test gap; transformer oil; voltage; Breakdown voltage; Charge carriers; Coaxial components; Current measurement; Electric breakdown; Oil insulation; Optical pulses; Pulse amplifiers; Testing; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2003. Annual Report. Conference on
Print_ISBN :
0-7803-7910-1
Type :
conf
DOI :
10.1109/CEIDP.2003.1254853
Filename :
1254853
Link To Document :
بازگشت