DocumentCode :
2423365
Title :
A study on the selection of outdoor insulators used in high altitude areas
Author :
Shi, W.D. ; Guan, Z.C. ; Wang, L.M. ; Zhou, J.
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear :
2003
fDate :
19-22 Oct. 2003
Firstpage :
391
Lastpage :
393
Abstract :
In recent years, large-scale development of China´s western region has been vigorously promoted. As part of the development, several very high voltage transmission lines have been or are planning to be built in China´s western region with a high altitude. The contamination flashover of insulators depends not only on the severity and type of contamination, but also on the altitude at which these insulators are situated. Reduced pressure or air density combined with light contamination at high altitudes decrease the flashover voltage. This paper analyzes the affects of low air pressure on the insulation characters of the transmission lines theoretically and experimentally, and a suggestion is given for the selection of outdoor insulator that will be used in the 110 kV AC power transmission line along Qinghai-Tibet railway.
Keywords :
flashover; high-voltage engineering; insulator contamination; insulator testing; power overhead lines; 110 kV; Qinghai-Tibet railway; contamination flashover; high altitude areas; outdoor insulators; very high voltage transmission lines; Contamination; Flashover; Insulation; Insulator testing; Pollution; Power transmission lines; Rail transportation; Sea surface; Transmission line theory; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2003. Annual Report. Conference on
Print_ISBN :
0-7803-7910-1
Type :
conf
DOI :
10.1109/CEIDP.2003.1254875
Filename :
1254875
Link To Document :
بازگشت