DocumentCode :
2423608
Title :
Impulse voltage breakdown of argon+SF6 mixtures under non-uniform electric fields
Author :
Hiziroglu, H.R. ; Nutakki, A. ; Dincer, M.S.
Author_Institution :
Dept. of Electr. & Comput. Eng., Kettering Univ., Flint, MI, USA
fYear :
2003
fDate :
19-22 Oct. 2003
Firstpage :
448
Lastpage :
450
Abstract :
This experimental study addresses the behavior of binary mixtures of argon and sulfur hexafluoride in a rod-plane electrode configuration when subjected to impulse voltages. Positive-polarity, standard lightning impulse voltages (1.2-μs/50-μs) with different magnitudes were employed throughout the experiments. The percentage of SF6 in Ar was varied from 1% to 90% at a total gas pressure of 50 kPa and 100 kPa. The breakdown voltage of each gas mixture was recorded at 50% breakdown probability. Similar to our theoretical as well as experimental studies under static electric fields it is observed that the breakdown strength of Ar has increased dramatically when mixed with a small percentage of SF6. However, the breakdown voltages did increase monotonically but not dramatically for higher SF6 percentages.
Keywords :
SF6 insulation; argon; electric breakdown; gas mixtures; impulse testing; insulating materials; insulation testing; 1.2 to 50 mus; 100 kPa; 50 kPa; Ar+SF6 mixtures; Ar-SF6; breakdown voltage; impulse voltage breakdown; nonuniform electric fields; positive-polarity; rod-plane electrode configuration; standard lightning impulse voltages; Argon; Breakdown voltage; Circuits; Dielectric breakdown; Electrodes; Lightning; Nonuniform electric fields; Oscilloscopes; Sulfur hexafluoride; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2003. Annual Report. Conference on
Print_ISBN :
0-7803-7910-1
Type :
conf
DOI :
10.1109/CEIDP.2003.1254889