Title :
Identification and location of breakdown in windings
Author :
Gopalakrishnan, M. ; Paneerselvam, M.A. ; Kumaravelu, C. ; Shreeshankar, R.B. ; Jayashankar, V.
Author_Institution :
SVCE, India
Abstract :
It is possible to estimate the location of the fault based on a study of the resonant frequencies of the winding current. It is shown that the nearest neighbourhood rule based on a clustering approach provides a good framework for fault location. Additional signal acquisition in the form of the tank current can considerably simplify the identification of a fault to ground. Experimental investigations are performed in order to identify and locate breakdown in windings.
Keywords :
electric breakdown; fault diagnosis; fault location; transformer windings; breakdown; clustering approach; fault location; identification; nearest neighbourhood rule; resonant frequencies; signal acquisition; tank current; windings; Circuit faults; Coils; Electric breakdown; Fault diagnosis; Fault location; Frequency estimation; Lightning; Power transformer insulation; Power transformers; Resonant frequency;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2003. Annual Report. Conference on
Print_ISBN :
0-7803-7910-1
DOI :
10.1109/CEIDP.2003.1254906