• DocumentCode
    24327
  • Title

    Power-Swing Detection Using Moving Window Averaging of Current Signals

  • Author

    Rao, J. Ganeswara ; Kumar Pradhan, Ashok

  • Author_Institution
    Dept. of Electr. Eng., Indian Inst. of Technol., Kharagpur, Kharagpur, India
  • Volume
    30
  • Issue
    1
  • fYear
    2015
  • fDate
    Feb. 2015
  • Firstpage
    368
  • Lastpage
    376
  • Abstract
    Power-swing blocking (PSB) function is necessary for the distance relay to avoid unwanted tripping of the transmission line. A power swing detection technique is proposed in this paper using a moving window averaging technique. The moving average of modulated current signal during power swing varies periodically whereas on inception of a fault, it remains either in positive or negative half. Using this property, two indices are calculated based on sign and time criteria of the moving average in order to distinguish the power swing from the balanced fault. The method is tested for numerous swing and fault conditions of a two-area four machine and WSCC 9-bus systems and compared with conventional methods.
  • Keywords
    moving average processes; power transmission faults; power transmission lines; PSB function; WSCC 9-bus systems; balanced fault; current signals; fault inception; modulated current signal; moving window averaging; power swing blocking function; power swing detection; transmission line; two-area four machine; unwanted tripping; Fault detection; Impedance; Protective relaying; Resistance; Steady-state; Trajectory; Distance relay; moving window averaging technique; power swing; transmission-line faults;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2014.2342536
  • Filename
    6876226