Title :
Generator field overvoltages due to energizing lines
Author :
Wang, Hongtao ; Liu, Yutian
Author_Institution :
Sch. of Electr. Eng., Shandong Univ., China
Abstract :
The field current transient characteristics are studied in the paper when generators energize transmission lines under no-load. The tendency of reverse current induced in field circuit is explained. Taking into account the effect of rotor eddy currents, a transient equivalent circuit of generator is presented. A generator energizing a 500 kV long line under no-load is simulated using the EMTDC program. The simulation results demonstrate that large reverse voltages may occur in field circuit and happen easier than the phenomena of self-excitation and switching surge overvoltages, and that the 4-quadrant excitation system can avoid the large reverse voltages.
Keywords :
AC generators; EMTP; eddy currents; equivalent circuits; overvoltage; power system restoration; power system transients; power transmission lines; rotors; surges; switching; 4-quadrant excitation system; 500 kV; EMTDC program; field circuit; field current transient characteristics; field loop; generator field overvoltages; large reverse voltages; lines energisation; no-load conditions; power system restoration; power system transients; reverse current; reverse voltages avoidance; rotor eddy currents; self-excitation; simulation results; switching surge overvoltages; transient equivalent circuit; Character generation; Circuit simulation; Distributed parameter circuits; EMTDC; Eddy currents; Equivalent circuits; Power system transients; Rotors; Surges; Voltage;
Conference_Titel :
Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
Print_ISBN :
0-7803-7459-2
DOI :
10.1109/ICPST.2002.1047156