Abstract
This paper presents the theoretical analysis of intermittent mal-operation of sensitive directional earth fault relays when switching off/on load and simulation tests based on Real Time Digital Simulator (RTDS). The magnitude of the residual current and voltage is dependent upon the load level and power factor, system source and line impedance´s, system capacitance to ground and the location of the open circuit. This paper analyses the effect of all electrical quantity to the problem. Based on the test results, the conclusion of mal-operation is drawn.
Keywords
earthing; load (electric); power system analysis computing; power system faults; power system protection; power system relaying; relay protection; switching; RTDS; Real Time Digital Simulator; computer simulation; intermittent mal-operation; load switching condition; open circuit; sensitive directional earth fault; Analytical models; Circuit faults; Circuit simulation; Circuit testing; Digital relays; Earth; Impedance; Power system relaying; Reactive power; Voltage;