• DocumentCode
    2447589
  • Title

    Using of additional earthing of affected phase for limitig of the touch voltage during earth faults in MV large compensated networks

  • Author

    Toman, Petr ; Dvorak, J. ; Orsagova, J. ; Topolanek, David

  • Author_Institution
    Brno Univerrsity of Technology
  • fYear
    2012
  • fDate
    23-26 April 2012
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Distribution system operator (DSO) sometimes needs to operate the large network which means operating of the network with big capacitive current (in Czech Republic more than 800A). This operation puts the emphasis not only on the setting of the earth fault relays but on the safety of the point of fault too. The paper describes the theoretical analysis, simulation and tests in real compensated distribution network with capacitive current 820A. There were tested low-ohmic and arc fault. The first results show that this type of operation is possible with using of the automatics of additional earthing of affected phase. The touch and step voltages were reduced under level allowed by standard EN 50522.
  • Keywords
    Earth; Fault currents; Grounding; Impedance; Resistance; Substations; Voltage measurement; Earth fault; power system safety; touch voltage;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on
  • Conference_Location
    Birmingham, UK
  • Print_ISBN
    978-1-84919-620-8
  • Type

    conf

  • DOI
    10.1049/cp.2012.0101
  • Filename
    6227589