Abstract :
This paper presents a new impedance based fault location method in the case of phase to phase and three phase faults. This method utilized the measured impedance by distance relay and super imposed current factor, which is the ratio of post-fault current to super imposed current, to discriminate the fault position on the line. This method is robust against the fault resistance. The presented method only uses the measured impedance by distance relay, the super imposed current factor and few data which could be achieved through the SCADA based databases.
Keywords :
Circuit faults; Electrical resistance measurement; Fault location; Impedance; Impedance measurement; Resistance; Transmission line measurements; Fault location; Impedance based method; Measured impedance; Transmission line;