Title
Study on backup protection for traction transformer
Author
Liu, Shuping ; Hu, Xiaoxiang ; Gao, Shibin ; Bo, Zhiqian
Author_Institution
School of Electrical Engineering, Southwest Jiaotong University, Chengdu, Sichuan, 610031, China
fYear
2012
fDate
23-26 April 2012
Firstpage
1
Lastpage
4
Abstract
At present, gas protection and current differential protection are generally used as the main protection for traction transformer in China high-speed railway. Overcurrent protection with busbar low-voltage start-up is used as the backup protection installed at HV side and LV side of transformer. This paper introduces the principle of overcurrent protection with busbar low-voltage start-up, and then analyses its advantages and disadvantages. According to the equivalent circuit model of the traction power supply system, this paper discusses the applicable condition of overcurrent protection with busbar low-voltage start-up, and analyses the misoperation possibility of the protection when there are remote end faults or large fault resistance. Based on the requirements of backup protection for traction power supply system, a backup protection scheme is introduced in this paper. In the scheme, a two-stage overcurrent protective relay is configured as the HV side backup protection for transformer, and a distance protective relay is used as the LV side backup protection.
Keywords
Circuit faults; Delay; Impedance; Power transformers; Protective relaying; Rail transportation; Substations; AC electrified railway; Backup protection; Distance protection; Overcurrent protection; Traction transformer;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on
Conference_Location
Birmingham, UK
Print_ISBN
978-1-84919-620-8
Type
conf
DOI
10.1049/cp.2012.0134
Filename
6227622
Link To Document