• DocumentCode
    2448578
  • Title

    Control of the single-phase customer-end inverter in a low-voltage DC distribution network

  • Author

    Peltoniemi, Pasi ; Nuutinen, Pasi ; Niemelä, Markku ; Pyrhönen, Juha

  • Author_Institution
    Dept. of Electr. Eng., Lappeenranta Univ. of Technol., Lappeenranta
  • fYear
    2008
  • fDate
    10-13 Nov. 2008
  • Firstpage
    635
  • Lastpage
    640
  • Abstract
    Proportional-integration (PI) controller scheme is implemented to control the phase voltage of the customer-end single-phase inverter in a low-voltage DC (LVDC) distribution system. In the inverter output, the LC-filter is used. In order to avoid resonances caused by the filter, the feedback and the feedforward filteration is used. It is shown that basic PI control system cannot drive the steady-state capacitor (load) voltage amplitude error to zero. To compensate the error, an outer-loop RMS voltage control is applied. The study shows that the system behaviour using a PI control is quite good.
  • Keywords
    PI control; distribution networks; invertors; power filters; voltage control; LC-filter; PI controller; feedback; feedforward filteration; low-voltage DC distribution network; outer-loop RMS voltage control; phase voltage control; proportional-integration controller; single-phase customer-end inverter; steady-state capacitor voltage amplitude error; Control systems; Error correction; Feedback; Filters; Inverters; Pi control; Proportional control; Resonance; Steady-state; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics, 2008. IECON 2008. 34th Annual Conference of IEEE
  • Conference_Location
    Orlando, FL
  • ISSN
    1553-572X
  • Print_ISBN
    978-1-4244-1767-4
  • Electronic_ISBN
    1553-572X
  • Type

    conf

  • DOI
    10.1109/IECON.2008.4758028
  • Filename
    4758028