DocumentCode
2455158
Title
Analysis of indoor thermal environment and heat loss of radiant floor heating system
Author
Ren, Yanli ; Li, Deying
Author_Institution
Biochem. Eng. Coll., Beijing Union Univ., Beijing, China
fYear
2011
fDate
24-26 June 2011
Firstpage
3822
Lastpage
3825
Abstract
According to characteristics of thermal process in heating room, the dynamic thermal model of radiant floor heating room was set up, and numerically solved by finite volume method. For radiant floor heating room and radiator heating room, numerical calculation results indicated that under the condition of arriving the same thermal comfort as radiator heating room, the design indoor air temperature of radiant floor heating system can be reduced by 2-4°C, and that radiant floor heating system can save 10%-30% energy compared with radiator heating system.
Keywords
finite volume methods; floors; heat losses; heat radiation; space heating; dynamic thermal model; energy saving; finite volume method; heat loss; indoor air temperature; numerical calculation; radiant floor heating room; radiant floor heating system; radiator heating room; thermal comfort; thermal process; Educational institutions; Floors; Heat engines; Heat transfer; Heating; Thermal analysis; Thermal engineering; heat loss; indoor thermal environment; radiant floor heating; radiator heating;
fLanguage
English
Publisher
ieee
Conference_Titel
Remote Sensing, Environment and Transportation Engineering (RSETE), 2011 International Conference on
Conference_Location
Nanjing
Print_ISBN
978-1-4244-9172-8
Type
conf
DOI
10.1109/RSETE.2011.5965072
Filename
5965072