DocumentCode :
2462439
Title :
Reignition phenomena after high-frequency current interruption in vacuum at small contact gaps
Author :
Weinert, Holger
Author_Institution :
Tech. Hochschule Aachen, Germany
Volume :
2
fYear :
1998
fDate :
17-21 Aug 1998
Firstpage :
541
Abstract :
Based on a large number of measurements of high-frequency (HF) current interruptions in a vacuum at small contact gap (⩽600 μm) the statistical reignition behaviour of vacuum switching devices after a HF current zero is investigated. Three types of reignitions can be classified. Statistical evaluation of post arc current measurements for different parameters at current zero, i.e. ignition of the HF current, current steepness and gap distance gives information about the stress of the gap as a result of the transient recovery voltage after a HF current zero (HF-TRV) and the accumulated post arc charge. Comparing post arc current values at the beginning of the HF-TRV and at the moment of reignition reveals a production of charge carriers during the recovery interval. Possible reasons for the different types of reignitions are discussed
Keywords :
circuit-breaking arcs; electric current measurement; switchgear testing; vacuum arcs; vacuum interrupters; HF current zero; charge carriers production; current steepness; gap distance; high-frequency current interruption; post arc charge accumulation; post arc current; reignition phenomena; small contact gaps; statistical reignition behaviour; transient recovery voltage; vacuum interrupter; vacuum switching devices; Capacitance; Circuits; Current measurement; Dielectric breakdown; Frequency; Hafnium; Ignition; Stress; Switches; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 1998. Proceedings ISDEIV. XVIIIth International Symposium on
Conference_Location :
Eindhoven
ISSN :
1093-2941
Print_ISBN :
0-7803-3953-3
Type :
conf
DOI :
10.1109/DEIV.1998.738709
Filename :
738709
Link To Document :