DocumentCode :
2468024
Title :
A review of the formation of S/sub 2/F/sub 10/ in gas insulated equipment
Author :
Chu, F.Y. ; Sauers, I. ; Griffin, G.D.
Author_Institution :
Ontario Hydro Res. Div., Toronto, Ont., Canada
fYear :
1988
fDate :
5-8 June 1988
Firstpage :
131
Lastpage :
134
Abstract :
The formation of S/sub 2/F/sub 10/ under high-power arc, spark or corona conditions in SF/sub 6/-insulated equipment is reviewed. It is shown that S/sub 2/F/sub 10/ is likely to be found in low-energy discharges such as spark or corona. Recent findings of trace amounts in high-power arcs raise concern for health and safety and call for further research. It is pointed out that future investigations must take into account factors such as gas impurities and moisture in the practical environment. Ultrasensitive techniques to detect the formation of S/sub 2/F/sub 10/ in gas-insulated equipment are required.<>
Keywords :
arcs (electric); corona; electric breakdown of gases; gaseous insulation; sparks; spectrochemical analysis; sulphur compounds; FT IR spectra; S/sub 2/F/sub 10/ formation; SF/sub 6/; corona; gas impurities; gas insulated equipment; high-power arc; low-energy discharges; moisture; review; safety; spark; toxicity; ultrasensitive techniques; Chemical products; Corona; Gas insulation; Guidelines; Health and safety; Impurities; Laboratories; Moisture; Personnel; Sparks;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1988., Conference Record of the 1988 IEEE International Symposium on
Conference_Location :
Cambridge, MA, USA
ISSN :
1089-084X
Type :
conf
DOI :
10.1109/ELINSL.1988.13886
Filename :
13886
Link To Document :
بازگشت