DocumentCode
2468277
Title
Demonstration of adaptive overcurrent protection using IEC 61850 communications
Author
Coffele, Federico ; Blair, Steve ; Booth, Campbell ; Kirkwood, John ; Fordyce, Bob
Author_Institution
PNDC, Univ. of Strathclyde, Glasgow, UK
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
This paper contains a description of an adaptive protection scheme that has been implemented and demonstrated in a hardware in the loop simulation environment using commercially available protection hardware and IEC 61850 communications. The implementation is based on an actual 11kV system which includes distributed generation and network automation. IEC 61850 communications offers several benefits for the implementation of adaptive protection, but also presents some limitations which are discussed in the paper. An alternative approach to overcome a number of the limitations is also presented.
Keywords
distributed power generation; overcurrent protection; substation automation; substation protection; IEC 61850 communications; adaptive overcurrent protection scheme; distributed generation; loop simulation environment; network automation; voltage 11 kV;