DocumentCode :
2468946
Title :
Dynamic tap-changer testing, reactors and reactance
Author :
Andersson, Goran ; Levi, Raka ; Osmanbasic, Edis
Author_Institution :
ABB Components, ABB AB, Västerås, Sweden
fYear :
213
fDate :
10-13 June 213
Firstpage :
1
Lastpage :
4
Abstract :
Dynamic resistance measurement (DRM) - a diagnostic technique that has recently been attracting a lot of attention due to its capability to detect On-load tap-changers (OLTC) problems - is discussed in this paper as applied to variable shunt reactors (VSR). Specific features in the current traces are explained. In addition, there is discussion of principles and DRM features as well as presentation of defect cases for reactance type of tap-changers tested using DRM methodology.
Keywords :
electric resistance measurement; on load tap changers; reactors (electric); DRM features; DRM methodology; OLTC; VSR; defect case presentation; diagnostic technique; dynamic resistance measurement; dynamic tap-changer testing; on-load tap-changers; tap-changer reactance type; variable shunt reactors;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location :
Stockholm
Electronic_ISBN :
978-1-84919-732-8
Type :
conf
DOI :
10.1049/cp.2013.0680
Filename :
6683283
Link To Document :
بازگشت