• DocumentCode
    2469862
  • Title

    Design of a 250 Amp telecom rectifier with true three-phase unity power factor input rectification stage

  • Author

    Keller, Markus

  • Author_Institution
    Ascorn Energy Syst., Bern, Switzerland
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    94
  • Lastpage
    100
  • Abstract
    This paper presents the design of a 14 kW three-phase 400/480 Vac input telecom rectifier module with 56 Vdc/250 Adc output current. A three level input rectification stage with sinusoidal input current is discussed in detail. All the control functionality is implemented by using a digital signal processor (DSP). The design of the digital controller is carried out entirely in z-domain. Simulation results and measurements with prototypes demonstrate the validity of the theoretical results.
  • Keywords
    power factor; rectifying circuits; telecommunication power supplies; 14 kW; 250 A; 300 to 530 V; 400 V; 480 V; 56 V; control functionality; digital controller design; digital signal processor; sinusoidal input current; telecom rectifier; three level input rectification stage; three-phase unity power factor input rectification stage; z-domain; Capacitors; Circuits; Digital signal processors; Inductors; Power system harmonics; Reactive power; Rectifiers; Switches; Telecommunication control; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
  • Print_ISBN
    0-7803-7512-2
  • Type

    conf

  • DOI
    10.1109/INTLEC.2002.1048640
  • Filename
    1048640