DocumentCode
2470249
Title
Can a battery ohmic tester distinguish a good cell from the pool of better ones?
Author
Noworolski, Zbig ; Reskov, Peng Ulo
Author_Institution
Polytronics Eng. Ltd., Toronto-Markham, Ont., Canada
fYear
2002
fDate
2002
Firstpage
221
Lastpage
226
Abstract
The correlation data between ohmic measurements and normalized capacity of a battery, published by various authors, is compiled and statistically analyzed for correlation factors in 5 regions between 0 and 100%. Weak correlations have been observed for some normalized capacity regions. An attempt has been made to provide a theoretical explanation for these discrepancies based on conductivity of the acid and the effect of temperature. In conclusion, the adequacy of the method (of ohmic measurements) is discussed.
Keywords
battery testers; lead acid batteries; statistical analysis; Pb; VLRA batteries; acid conductivity; battery ohmic tester; normalized battery capacity; ohmic measurements; temperature effect; Battery charge measurement; Conductivity; Costs; Electric resistance; Electrical resistance measurement; Impedance measurement; Instruments; Manufacturing; Statistical analysis; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
Print_ISBN
0-7803-7512-2
Type
conf
DOI
10.1109/INTLEC.2002.1048660
Filename
1048660