• DocumentCode
    2470504
  • Title

    Vacuum circuit breakers in cable networks

  • Author

    Schellekens, Hans ; Shulepov, Igor ; Tobias, Juan

  • Author_Institution
    Schneider Electr., Grenoble, France
  • fYear
    213
  • fDate
    10-13 June 213
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The impact of switching over-voltages in a public distribution network on cable ageing and the occurrence of earth fault failure are discussed. It is concluded that 95% of the network remains unaffected by the behaviour of the VCB, and that switching over-voltages in the remaining connected Industrial sites don´t propagate into the public network. Hence, VCB behaviour cannot explain the increased earth fault failure rate observed in Russia.
  • Keywords
    earthing; overvoltage protection; power cables; power distribution faults; power distribution protection; vacuum circuit breakers; VCB; cable network ageing; earth fault failure occurrence; public distribution network; switching overvoltages impact; vacuum circuit breaker;