DocumentCode :
2471318
Title :
Testing personal protective grounds
Author :
Blackley, W.P. ; Crouse, George
Author_Institution :
Associated Training Corp., Irving, TX, USA
fYear :
1998
fDate :
26-30 April 1998
Firstpage :
115
Lastpage :
118
Abstract :
Personal Protective Grounds, Ground Sets or "Ground Chains" are intended to provide protection to the electrical worker by maintaining a sufficiently low voltage across an individual in the event of unexpected line energization. Energization can occur from numerous sources including lightning, falling conductors and operational errors such as closing the wrong switch or breaker. Generally 50 volts is the accepted level (although some organizations may allow 75 volts) that must not be exceeded across the worker and thus the protective ground set during such conditions. In an effort to assure themselves of a ground sets integrity it is becoming common place for companies to test personal protective ground sets. Since many organizations do not have high current test facilities that can be used to test at such elevated currents, low current testing and extrapolation of low current test results may be desirable, especially if numerous ground sets are to be tested. This paper points out that in and of itself low current testing of protective grounds is not a sufficient method to qualify grounds as safe, adequate or good.
Keywords :
earthing; protection; safety; testing; Ground Chains; Ground Sets; electrical worker protection; falling conductors; ground sets integrity; lightning; low current testing; low voltage; operational errors; personal protective grounds testing; unexpected line energization; Cables; Clamps; Conducting materials; Conductors; Fault currents; Fibrillation; Impedance; Protection; Switches; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission & Distribution Construction, Operation & Live-Line Maintenance Proceedings, 1998. ESMO '98. 1998 IEEE 8th International Conference on
Conference_Location :
Orlando, FL, USA
Print_ISBN :
0-7803-4883-4
Type :
conf
DOI :
10.1109/TDCLLM.1998.668340
Filename :
668340
Link To Document :
بازگشت