• DocumentCode
    2471381
  • Title

    Considerations on rectifier sizing

  • Author

    Rousseau, Yves ; Mongrain, Claude

  • Author_Institution
    Emerson Energy Syst., Montreal, Que., Canada
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    596
  • Lastpage
    602
  • Abstract
    Having too much charging capacity in a power system can be as disastrous as not having enough. When provisioning the charging equipment for a power system, at least three important factors must be considered: the normal drain of the telecom equipment; the maximum recharge time of the batteries; and the maximum recharge current of the batteries. The first two factors are commonly considered, but very often the third one tends to be omitted, even though it can have dramatic effects on the cost of operation. This paper exposes in detail the consequences of improper rectifier sizing. It also discusses features now offered with many new power plant to control the recharge current and prevent some of the consequences listed above. It further exposes the consequences on battery protection (battery fuses or breaker sizes).
  • Keywords
    battery chargers; electric current control; rectifying circuits; secondary cells; telecommunication power supplies; battery fuses; battery protection; breaker sizes; charging capacity; maximum battery recharge current; maximum battery recharge time; normal drain; power system; recharge current control; rectifier sizing; telecom equipment; Batteries; Costs; Fuses; Heat sinks; Manufacturing; Power generation; Power system protection; Power systems; Rectifiers; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2002. INTELEC. 24th Annual International
  • Print_ISBN
    0-7803-7512-2
  • Type

    conf

  • DOI
    10.1109/INTLEC.2002.1048718
  • Filename
    1048718