Abstract :
The temperature of condensate water has greatly influenced on differential pressure level indicator in operation, which makes level measurement not accurate. When the change of drum pressure is very little, the compensation of drum level will be accurately carried out if the average temperature of condensate water can be measured. Data fusion technology is introduced into drum level compensation of the boiler in this paper, which uses arithmetic average in batch estimation to ensure the average temperature of condensate water so that the accuracy and reliability of drum level measurement can be obviously improved compared with arithmetic average method. It is proved that the method is valid by an example.
Keywords :
boilers; power engineering computing; sensor fusion; batch estimation; data fusion; drum level compensation method; Arithmetic; Boilers; Containers; Current measurement; Electrical resistance measurement; Intelligent control; Level control; Level measurement; Pressure measurement; Temperature measurement; data fusion; in batch estimation; level compensation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Intelligent Control and Automation, 2008. WCICA 2008. 7th World Congress on
Conference_Location :
Chongqing
Print_ISBN :
978-1-4244-2113-8
Electronic_ISBN :
978-1-4244-2114-5
Type :
conf
DOI :
10.1109/WCICA.2008.4592822
Filename :
4592822
Link To Document :
بازگشت