DocumentCode
2473274
Title
Continuous online monitoring of PD activity in the medium voltage distribution network
Author
Mulroy, Patrick ; Gilbert, Ian ; Hurtado, A.
Author_Institution
Ormazabal, Zamudio, Spain
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
Partial discharges (PD) occur as a result of dielectric breakdown in electrical insulation under high voltage stress. They can be caused by the presence of gas pockets or voids in solid insulation / gas bubbles in liquid insulators (internal), insulator surface imperfections / irregularities (superficial) and around an electrode in gas (corona). PD activity, once initiated, causes chemical and physical degradation of insulating material and can lead to catastrophic failure. Early warning of PD activity and localisation is considered essential to ensure the long term reliable operation of high voltage equipment including cables, cable accessories and switchgear. PD detection in high voltage cable and cable accessories is usually carried out with test objects offline, requiring potentially significant interruption of service. An online detection system is preferable but difficult to calibrate apparent charge magnitudes due to changes in real distribution network loading and topologies. An online PD monitoring system with continuous calibration has been developed to determine the apparent charge magnitudes of PD activity and locations in a section of an in-service distribution network. System components including the online calibration pulse injector, capacitive sensors for high frequency PD pulse detection, and data acquisition, processing and communication components at each monitoring site will be presented. Long term parameter trending data from the ongoing trial in a typical urban distribution network in Spain will also be presented.
Keywords
bubbles; cables (electric); calibration; computerised monitoring; data acquisition; distribution networks; insulation; insulators; partial discharges; power engineering computing; switchgear; PD activity; PD activity warning; PD detection; Spain; cable accessories; capacitive sensors; chemical degradation; continuous calibration; continuous online monitoring; corona; data acquisition; dielectric breakdown; electrical insulation; electrode; gas bubbles; gas pockets; high frequency PD pulse detection; high voltage equipment; high voltage stress; in-service distribution network; insulating material; insulator surface imperfections; irregularities; liquid insulators; localisation; medium voltage distribution network; online PD monitoring system; online calibration pulse injector; online detection system; partial discharges; physical degradation; solid insulation; switchgear; urban distribution network; voids;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location
Stockholm
Electronic_ISBN
978-1-84919-732-8
Type
conf
DOI
10.1049/cp.2013.0890
Filename
6683493
Link To Document