    Assessing hydrogen direct cooling electrical generators through on-line partial discharge measurements

  • Author

    Reyes, Oscar ; Robles, Edgar

  • Author_Institution
    Instituto de Investigaciones Electricas, Morelos, Mexico
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    495
  • Lastpage
    500
  • Abstract
    There are 22 direct cooled hydrogen generators operating in the Mexican Grid. Some of them have experienced outages due to critical failures. A brief description of the cooling system and the deterioration mechanisms is being reviewed in this article. Discharge measurements can be use to accurately determine the conditions of these generators. Partial Discharge activity can be recorded with the generator off-line during maintenance outages at different test voltages levels or on-line with the machine at different load conditions. The obtained results on a 346 MVA, 20 kV generator are reported. Measurements were taking on-line through the RTD´s connection box.
  • Keywords
    cooling; partial discharge measurement; power generation reliability; turbogenerators; 20 kV; 346 MVA; cooling system; critical failures; direct cooled hydrogen generators; on-line partial discharge measurements; outages; Conductors; Cooling; Electric variables measurement; Generators; Hydrogen; Nuclear power generation; Partial discharge measurement; Partial discharges; Stator windings; Voltage;