DocumentCode :
2475556
Title :
A novel on-line PD monitoring and diagnostic system for power transformers
Author :
Lin, D. ; Jiang, L. ; Li, F.Q. ; Zhu, D.H. ; Tan, K.X. ; Wang, C.C. ; Jin, X.H. ; Cheng, T.C. ; Wu, C.Q.
Author_Institution :
Tsinghua Univ., Beijing, China
fYear :
2002
fDate :
2002
Firstpage :
748
Lastpage :
751
Abstract :
This paper introduces a computerized online PD (Partial Discharge) monitoring and diagnostic system for power transformers, which has been installed in a 500 kV substation in China. It consists of wide-band active transducers and DAU (Data Acquisition Unit) with modularized and exchangeable components. This system has been developed to monitor multiple parameters of multiple power transformers, which is based on COM (Component Object Model). In addition, the system can also be used to monitor other power equipment. Some results of on-line monitoring are discussed.
Keywords :
partial discharge measurement; power transformer testing; component object model; computerized online monitoring; diagnostic system; partial discharge; power transformers; wide-band active transducers; Acoustic transducers; Bandwidth; Computerized monitoring; Condition monitoring; Data acquisition; Frequency; Partial discharges; Power system modeling; Power transformers; Wideband;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
Print_ISBN :
0-7803-7502-5
Type :
conf
DOI :
10.1109/CEIDP.2002.1048904
Filename :
1048904
Link To Document :
بازگشت