DocumentCode
2475573
Title
Studies on static charging behaviour of transformer oils
Author
Rajaraman, R. ; Mukherji, S. ; Suryanarayana, D. ; Adikesavulu, A.K. ; Murthy, T.S.R. ; Agashe, P.G.
Author_Institution
Bharat Heavy Electricals Ltd., Hyderabad, India
fYear
1993
fDate
17-20 Oct 1993
Firstpage
402
Lastpage
407
Abstract
Investigations on paraffinic oils are presented. Charge level measurements on a few paraffinic-based oils and a typical naphthenic-based oil are discussed. Most paraffinic oils were found to have high charge levels, which was attributed to higher ionic contamination and dominant chemical structure. While a charge suppressor reduced the charge levels of high charging oils, it had an adverse effect on other dielectric properties. However, its presence retarded ageing. Paraffinic oils from service transformers showed a significant deterioration in these properties compared to naphthenic oils
Keywords
static electrification; transformer oil; ageing; charge suppressor; chemical structure; dielectric properties; high charge levels; ionic contamination; naphthenic-based oil; paraffinic oils; static charging behaviour; transformer oils; Charge measurement; Conductivity; Current measurement; Density measurement; Dielectric loss measurement; Dielectric losses; Electrical capacitance tomography; Electrostatic measurements; Oil insulation; Petroleum;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1993. Annual Report., Conference on
Conference_Location
Pocono Manor, PA
Print_ISBN
0-7803-0966-9
Type
conf
DOI
10.1109/CEIDP.1993.378939
Filename
378939