Abstract :
A new type of relay suitable for the protection of wind farms has been described. The relay, installed at the utility end of a power collection circuit, is designed to protect the collection circuit and the LV and MV windings of each wind turbine generator transformer. The relay has been tested on-site at the Cemmaes wind farm and in a laboratory using the EMTDC simulator and an OMICRON relay test set. Numerous tests have shown that the relay remains stable during out-of-zone faults or nonfault disturbances and is sufficiently sensitive to operate on all realistic in-zone faults
Keywords :
wind power plants; Cemmaes wind farm; EMTDC simulator; LV windings; MV windings; OMICRON relay test set; in-zone faults; induction generators; nonfault disturbances; out-of-zone faults; power collection circuit; protection relay; wind farms; wind turbine generator transformer;