DocumentCode :
2477815
Title :
Locating defects in high voltage transmission lines
Author :
Jaensch, G. ; Hoffmann, H. ; Markees, Alf
Author_Institution :
Badenwerk AG, Durlacher Allee, Germany
fYear :
1998
fDate :
26-30 April 1998
Firstpage :
179
Lastpage :
186
Abstract :
Methods of locating defects in overhead high voltage and extra-high voltage transmission lines are described and evaluated. Included is a technology which utilizes corona partial discharge detection to find faulty conditions while simultaneously performing routine visual inspections from a helicopter. The corona inspection system proved to be very useful in locating broken strands, loose spacers, insulators with internal or external discharges, and other faulty line conditions.
Keywords :
corona; fault location; inspection; insulators; partial discharges; power overhead lines; EHV; HV; broken strands; corona partial discharge; defect location methods; faulty line conditions; helicopter; insulator discharges; loose spacers; overhead transmission lines; visual inspections; Corona; Fault detection; Helicopters; Inspection; Insulation; Partial discharges; Power overhead lines; Space technology; Transmission lines; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission & Distribution Construction, Operation & Live-Line Maintenance Proceedings, 1998. ESMO '98. 1998 IEEE 8th International Conference on
Conference_Location :
Orlando, FL, USA
Print_ISBN :
0-7803-4883-4
Type :
conf
DOI :
10.1109/TDCLLM.1998.668371
Filename :
668371
Link To Document :