DocumentCode :
2478106
Title :
Detection of single phase earth fault in compensated network with C0 estimation
Author :
Loos, Matthieu ; Werben, Stefan ; Kereit, Matthias ; Maun, Jean-Claude
Author_Institution :
Univ. Libre de Bruxelles, Brussels, Belgium
fYear :
213
fDate :
10-13 June 213
Firstpage :
1
Lastpage :
4
Abstract :
Single phase earth fault in compensated network creates faulty current with very small magnitude. The connection of a Petersen Coil in the transformer neutral turns the zero sequence impedance into very high ohmic system. The small faulty current makes the detection of the faulty feeder impossible with simple over current protection. That is why algorithms are using transients. This paper presents a novel method to detect such earth fault with a strong sensitivity regarding the fault impedance. The algorithm builds a model of the sound feeder behaviour using the zero sequence voltage and current. The healthy feeder can be considered as a zero sequence capacitance. By measuring the deviation of a perfectly capacitive feeder, the faulty one can be detected. Algorithm description and tests are presented with comparison of small impedance fault and high impedance with recordings and simulations.
Keywords :
fault diagnosis; overcurrent protection; power distribution faults; power distribution protection; power transformers; Petersen coil; capacitive feeder; compensated network; fault impedance; faulty current; faulty feeder; healthy feeder; overcurrent protection; single phase earth fault detection; sound feeder behaviour; transformer neutral; zero sequence capacitance; zero sequence current; zero sequence voltage;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location :
Stockholm
Electronic_ISBN :
978-1-84919-732-8
Type :
conf
DOI :
10.1049/cp.2013.1120
Filename :
6683723
Link To Document :
بازگشت