    Harmonic voltages and lightning equipment flicker caused by pumping station — Measurements, analysis and mitigation

  • Author

    Toftevaag, Trond ; Seljeseth, H. ; Paulsen, Rune

  • Author_Institution
    Energy Res., SINTEF, Trondheim, Norway
  • fYear
    213
  • fDate
    10-13 June 213
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper discusses cause and effect of harmonic voltages and severe lighting equipment flicker that were observed by low voltage end consumers in connection with the operation of a pumping station connected to a 22 kV radial line of a typical MV distribution network of a Norwegian utility. The pumping station, consisting of three wound-rotor induction motors rated at 1.75 MW, 6.6 kV, forms part of a local medium-size hydro power scheme. The voltage disturbance is a 7.harmonic (and partly 5.harmonic) component fluctuating with a frequency of approximately 2 Hz, resulting in considerable flicker problems in lighting equipment at end customers, causing customer complaints.
  • Keywords
    distribution networks; induction motors; lightning protection; pumped-storage power stations; rotors; MV distribution network; Norwegian utility; harmonic voltages; lightning equipment flicker; local medium-size hydro power scheme; low voltage end consumers; power 1.75 MW; pumping station; voltage 22 kV; voltage 6.6 kV; voltage disturbance; wound-rotor induction motors;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
  • Conference_Location
    Stockholm
  • Electronic_ISBN
    978-1-84919-732-8
  • Type

    conf

  • DOI
    10.1049/cp.2013.1152
  • Filename
    6683755