Harmonic voltages and lightning equipment flicker caused by pumping station — Measurements, analysis and mitigation
Author
Toftevaag, Trond ; Seljeseth, H. ; Paulsen, Rune
Author_Institution
Energy Res., SINTEF, Trondheim, Norway
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
This paper discusses cause and effect of harmonic voltages and severe lighting equipment flicker that were observed by low voltage end consumers in connection with the operation of a pumping station connected to a 22 kV radial line of a typical MV distribution network of a Norwegian utility. The pumping station, consisting of three wound-rotor induction motors rated at 1.75 MW, 6.6 kV, forms part of a local medium-size hydro power scheme. The voltage disturbance is a 7.harmonic (and partly 5.harmonic) component fluctuating with a frequency of approximately 2 Hz, resulting in considerable flicker problems in lighting equipment at end customers, causing customer complaints.
Keywords
distribution networks; induction motors; lightning protection; pumped-storage power stations; rotors; MV distribution network; Norwegian utility; harmonic voltages; lightning equipment flicker; local medium-size hydro power scheme; low voltage end consumers; power 1.75 MW; pumping station; voltage 22 kV; voltage 6.6 kV; voltage disturbance; wound-rotor induction motors;