• DocumentCode
    2479573
  • Title

    Portable dc circuit breaker calibrator using high frequency thyristor converter

  • Author

    Paice, Derek A.

  • Author_Institution
    Westinghouse Research and Development Center, Pittsburgh, Pennsylvania, USA
  • fYear
    1980
  • fDate
    16-20 June 1980
  • Firstpage
    226
  • Lastpage
    233
  • Abstract
    A portable calibrator to check the trip setting of direct current (dc)circuit breakers within an accuracy of ±5% has been developed and tested under Bureau of Mines Contract HO 122058. A prototype unit operates from a 300 Vdc trolley wire to provide controlled current pulses of 120 msec duration and continuously adjustable from 1,400 to 3,600 A. These current pulses enable a breaker dc trip current to be determined and subject the contacts to full current rating. The equipment is simple to use and weighs 93 lb. Connections are made with protected, clamp-on leads, which weigh about 21 lb. An accurate calibration procedure takes less than 5 minutes to complete.
  • Keywords
    Calibration; Capacitors; Circuit breakers; Inverters; Prototypes; Switches; Thyristors;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Specialists Conference, 1980. PESC. IEEE
  • Conference_Location
    Atlanta, Georgia, USA
  • ISSN
    0275-9306
  • Type

    conf

  • DOI
    10.1109/PESC.1980.7089453
  • Filename
    7089453