DocumentCode
2480925
Title
A procedure to evaluate the risk of failure of distribution transformers insulation due to lightning induced voltages
Author
Lopes, Gustavo P. ; Martinez, M.L.B. ; Borghetti, Alberto ; Napolitano, Fabio ; Nucci, Carlo Alberto ; Uchoa, Juliana I. L. ; Dos Santos, Gilnei J. G. ; Fagundes, Donorvan R.
Author_Institution
Fed. Univ. of Itajuba, Itajuba, Brazil
fYear
213
fDate
10-13 June 213
Firstpage
1
Lastpage
4
Abstract
The aim of the paper is to assess the risk of insulation failure of distribution transformers connected to overhead distribution due to indirect lightning induced voltages. The annual frequencies of occurrence of dangerous voltages are evaluated through a Monte Carlo procedure and by using the LIOV-EMTP code for the calculation of the Lightning Electromagnetic Pulse (LEMP) and its effects on the multiconductor line. The probability of distribution transformers insulation to withstand the stresses caused by lightning overvoltages is inferred from the results of experimental test.
Keywords
EMTP; Monte Carlo methods; lightning protection; multiconductor transmission lines; overvoltage; transformer insulation; LIOV-EMTP code; Monte Carlo; distribution transformers insulation; insulation failure risk; lightning electromagnetic pulse; lightning induced voltages; lightning overvoltages; multiconductor line; overhead distribution;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution (CIRED 2013), 22nd International Conference and Exhibition on
Conference_Location
Stockholm
Electronic_ISBN
978-1-84919-732-8
Type
conf
DOI
10.1049/cp.2013.1258
Filename
6683861
Link To Document