Abstract
Many power cables with extruded insulation installed in the 1970s are approaching the end of their manufacturer´s design life. Cable replacement strategies based solely on cable age, insulation type, and average failure rates seem inadequate given shrinking capital and maintenance budgets, on the one hand, and a greater demand for improved reliability, on the other hand. This is particularly challenging in the management of an aging population of extruded cables in underground residential distribution (URD) systems. A condition-based cable management program has been developed to replace cables only where needed and to closely monitor cables remaining in service. The program relies on off-line partial discharge (PD) technology to assess the condition of extruded URD cables that have been in service for as long as 40 years. Cables are selected for PD measurement based on historical performance and vintage. The test results are used to assist in making asset management decisions such as replacement, repair, and rejuvenation. This paper describes the URD cable condition assessment program and presents the results from a pilot program conducted on an URD primary distribution system serving a number of densely populated neighborhoods in a suburban area of Metropolitan New York. It also discusses the challenges encountered and measures developed to overcome them during the pilot program.
Keywords
ageing; partial discharge measurement; power cable insulation; underground cables; underground residential distribution systems; Metropolitan New York; PD measurement; URD cable condition assessment program; URD primary distribution system; aging population; asset management decisions; average failure rates; cable age; cable replacement strategies; condition-based cable management program; densely populated neighborhoods; design life; extruded insulation; extruded underground residential distribution cables; insulation type; maintenance budgets; off-line partial discharge technology; pilot program; power cables; shrinking capital; suburban area; Joints; Maintenance engineering; Partial discharges; Power cable insulation; Power cables; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2012 Annual Report Conference on
Conference_Location
Montreal, QC
ISSN
0084-9162
Print_ISBN
978-1-4673-1253-0
Electronic_ISBN
0084-9162
Type
conf
DOI
10.1109/CEIDP.2012.6378741
Filename
6378741
Link To Document