• DocumentCode
    2484384
  • Title

    Analysis of integral snubber circuit design for transformers in urban high rise office building

  • Author

    Sutherland, Peter E.

  • Author_Institution
    Ind. Solutions, GE Energy Services, Schenectady, NY, USA
  • fYear
    2012
  • fDate
    20-24 May 2012
  • Firstpage
    1
  • Lastpage
    17
  • Abstract
    Transformer failures have in recent years led to the development of Resistor-Capacitor snubber circuits for the protection of the transformer and winding insulation from the damaging effects of high-voltage high-frequency transients. Transformer insulation may be damaged if the Basic Insulation Level (BIL) is exceeded, turn-to-turn insulation when there is excessive rate of change of voltage with time (dv/dt), and to switching devices by restrikes when the Transient Recovery Voltage (TRV) is exceeded. These transients are most often observed when dry-type transformers are close coupled to vacuum switching devices. Some manufacturers are now including snubbers in their transformer designs. This paper provides a thorough review of the causes of the transients, methods of analysis, and mitigation of the effects of these transients. An example is provided of transformers to be installed in the basement of an urban high rise office building, where the space is limited and the available fault current is high, where the transformer enclosure includes built-in snubber circuits. The strengths and weaknesses of current methods are examined. Recommendations are made for improvements in snubber circuit design and analysis.
  • Keywords
    failure analysis; fault currents; snubbers; transformer insulation; transformer protection; TRV; basic insulation level; damaging effects; dry-type transformers; fault current; high-voltage high-frequency transients; integral snubber circuit design analysis; resistor-capacitor snubber circuits; transformer enclosure; transformer failures; transformer insulation; transformer protection; transient recovery voltage; turn-to-turn insulation; urban high rise office building; vacuum switching devices; Cable insulation; Cable shielding; Conductors; Switches; Snubbers; Transformer failure; Transformer protection; Transformer snubber circuits; Transient analysis; Transient overvoltages; Transient rate of rise of voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial & Commercial Power Systems Technical Conference (I&CPS), 2012 IEEE/IAS 48th
  • Conference_Location
    Louisville, KY
  • ISSN
    2158-4893
  • Print_ISBN
    978-1-4673-0652-2
  • Type

    conf

  • DOI
    10.1109/ICPS.2012.6229607
  • Filename
    6229607