DocumentCode :
2486049
Title :
Coconut oil as transformer liquid insulation — Ageing and simulated thermal and electrical faults
Author :
Matharage, B. S H M S Y ; Fernando, M.A.R.M. ; Tuncer, E. ; Bandara, M.A.A.P. ; Kalpage, C.S.
Author_Institution :
Fac. of Eng., Univ. of Peradeniya, Peradeniya, Sri Lanka
fYear :
2012
fDate :
14-17 Oct. 2012
Firstpage :
839
Lastpage :
842
Abstract :
This paper presents performance comparison of coconut oil as an alternative liquid insulation for transformer mineral oil during ageing and under simulated electrical and thermal fault conditions. In the ageing study, 6 wet coconut oil, 6 wet and 6 dry transformer oil samples were aged (each half as sealed and unsealed with inclusions of Cu, Al, Fe and Zn metal substances) inside an oven at 120°C. Six sample sets were taken out at three different ageing intervals i.e. 2, 5 and 7 weeks and were tested by visual inspection (color), chemical tests (interfacial tension, acidity, DGA) and electrical tests (breakdown voltage, FDS). In the electrical fault study, 2 coconut oil and 2 transformer oil samples were exposed to corona for four hours and for 20 electrical breakdowns with a point-plane gap of 15mm. In the thermal fault study, 2 coconut oil and 2 transformer oil samples were aged at 160°C for 12 hours and at 200°C for 1 hour. The DGA and FDS measurements were taken on the aged samples. FDS Results were analyzed by using Davidson-Cole Model. It was found that the coconut oil samples gave comparable results with those for transformer oil.
Keywords :
ageing; aluminium; chemical analysis; copper; essential oils; fault diagnosis; iron; transformer oil; zinc; Al; Cu; DGA measurement; Davidson-Cole model; FDS measurement; Fe; Zn; acidity; ageing intervals; ageing thermal-electrical faults; aluminum metal substance; breakdown voltage; chemical tests; coconut oil; color; copper metal substance; corona; electrical breakdowns; electrical tests; interfacial tension; iron metal substance; point-plane gap; simulated thermal-electrical faults; temperature 120 degC; temperature 160 degC; temperature 200 degC; time 1 hour; time 12 hour; time 2 week; time 5 week; time 7 week; transformer liquid insulation; transformer mineral oil; visual inspection; zinc metal substance; Aging; Conductivity; Dielectric liquids; Image color analysis; Oil insulation; Power transformer insulation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2012 Annual Report Conference on
Conference_Location :
Montreal, QC
ISSN :
0084-9162
Print_ISBN :
978-1-4673-1253-0
Electronic_ISBN :
0084-9162
Type :
conf
DOI :
10.1109/CEIDP.2012.6378911
Filename :
6378911
Link To Document :
بازگشت