    The total hydrocarbon ampere-volt method

  • Author

    Zhou, Yang Min ; Hong, Yang

  • Author_Institution
    Power Distribution Bur., Guangxi, China
  • fYear
    1998
  • fDate
    27-30 Sep 1998
  • Firstpage
    775
  • Lastpage
    778
  • Abstract
    With overheating in the magnetic circuit, the total hydrocarbon content in a transformer is proportional to the square of the applied voltage while it is proportional to the square of the current when overheating occurs in the conductor circuit. In the paper, the total hydrocarbon ampere-volt method (THAVM) is introduced. The object of THAVM is to locate fault position by analyzing the relations between the total hydrocarbon content and the current or the applied voltage. It has proved this method is simple and economically feasible
  • Keywords
    fault location; power transformer testing; transformer magnetic circuits; transformer oil; conductor circuit; fault location; magnetic circuit; overheating; total hydrocarbon ampere-volt method; total hydrocarbon content; transformer oil; Circuit faults; Circuit testing; Conductors; Dissolved gas analysis; Hydrocarbons; Iron; Oil insulation; Petroleum; Power transformer insulation; Transformer cores;