DocumentCode
2505486
Title
Wide area measurement based out-of-step detection technique
Author
Kundu, Pratim ; Rao, J. Ganeswara ; Nayak, P.K. ; Pradhan, A.K.
Author_Institution
Dept. of Electr. Eng., IIT Kharagpur, Kharagpur, India
fYear
2010
fDate
20-23 Dec. 2010
Firstpage
1
Lastpage
5
Abstract
The electrical power systems function as a huge interconnected network dispersed over a large area. A balance exist between generated and consumed power, any disturbance to this balance in the system caused due to change in load as well as faults and their clearance often results in electromechanical oscillations. As a result there is variation in power flow between two areas. This phenomenon is referred as Power Swing. This paper uses PMU data to measure the currents and voltages of the three phases of two buses connected to a 400 kV line. The measured data is then used for differentiating between a swing or fault condition, and if a swing is detected, to predict whether the swing is a stable or an unstable one. The performance of the method has been tested on a simulated system using PSCAD and MATLAB software.
Keywords
load flow; oscillations; power system faults; power system interconnection; power system measurement; MATLAB software; PMU data; PSCAD; electrical power systems function; electromechanical oscillations; fault condition; huge interconnected network; out-of-step detection technique; power flow; power swing; voltage 400 kV; wide area measurement; Phasor measurement units; Time measurement; Transforms; DFT; Phasor Measurement Units; phase difference;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics, Drives and Energy Systems (PEDES) & 2010 Power India, 2010 Joint International Conference on
Conference_Location
New Delhi
Print_ISBN
978-1-4244-7782-1
Type
conf
DOI
10.1109/PEDES.2010.5712569
Filename
5712569